Saudi Journal of Civil Engineering (SJCE)
Volume-6 | Issue-04 | 79-94
Original Research Article
Static Pullout Tests on Retrofitted Anchorage System in Concrete Using Supplementary Reinforcement
Padmanabham K, Rambabu K
Published : April 15, 2022
Abstract
This paper presents experimental results of retrofitted anchorage system of structural concrete by using Post-Installation of Supplementary Anchorage (PISA) as a implicit strengthening measure and to improve the nonlinear performance of conventional anchorage system in hardened concrete. A total sixty specimens of M25 grade concrete (150x150x300mm) with two different size of rebar anchorage of 12mm, 16mm and five different configuration of conventional anchorage system was retrofitted by PISA technique is verified under direct tension pullout quasi static loads. The configuration of anchorage comprised by straight bar (A1), 90degree bend (A2), 180degree hook (A3), single head bar (A4) and double head bar (A5). The test parameters considered are bond strength, ductility, stiffness and bar-slip and test variables are configuration of anchorage, size of rebar and presence of supplementary steel. The obtained results validated by ANSYS modeling. This study concludes that a considerable improvement of nonlinear parameters such as ultimate load (3-8%), stiffness (4%-17%), ductility (16%-52%) and concrete contribution (6%-23%) by using PISA technique.